NPPA-TT-S Instruction Manual
4. Grounding variations
The flexible grounding system provides the following versions:
Individual: Each channel is individually grounded by its corresponding cable shield
(default configuration).
Group: Selected channel grounds are connected via the ground bus on the
PCB using solder bridges and track cuts to form a group that is
connected to one common cable shield.
Central: All channel grounds (individual top and bottom row) are connected via
the ground bus on the PCB using solder bridges and wired with only
one cable shield.
Chassis-Common: The same as central grounding but with the addition of the common
ground bus (top and / or bottom rows) connected to the patch panel
chassis by means of jumpers.